GPR-M250-12V

High Voltage DC contactor 250Amps, 1000VDC (DC relay). The relay is perfect for applications in automotive, solar, ups, Energy Storage Systems, etc. The magnets take care for the arc blowout. Coil voltage 12VDC.

Share:

Downloads

To get a more deep overview of the total GPR product line, please download one of the pdf’s below:

Download Leaflet GPR Relays

Download Extended Catalog GPR-Series



Specifications (Key features)

Number of poles 1 pole
Operating Voltage up to 1000VDC
Coil voltage 12VDC
Rated impulse withstand voltage, U imp 6kV
Conventional thermal Current, Ith 250 Amps
Shorttime withstand current 2 min: 500 Amps
Unnamed variable 15 min: 350 Amps
Mechanical durability > 200.000 cycles
Electrical durability 125A, 1000VDC, 1.000cycles (at 360 cycles/Hr)
Voltage drop 0.02V@20Amps
Operating time Max. 30ms
Release time Max. 10ms
Insulation strength (initial) Min. 100MΩ (@1000VDC)
Size, W × H × D( mm ) 92x45x87
Temperature range -40 – 85C
Humidity 5-95% R.H.
Weight 500 gr
Certification CE, UL, CCC

enquiry form

Enquire now about the GPR-M250-12V